ADG-530Hot Surface Ignition (HSI) SystemTechnical ManualAmerican Dryer Corporation88 Currant RoadFall River MA 02720-4781Telephone: (508) 678-9000 / F
8TEST EQUIPMENTThe following pieces of test equipment will be required to troubleshoot this system withminimal time and effort.1. HSI (Hot Surface Ign
9There are two (2) types of devices used tomeasure water column (W.C.) pressure.They are the spring/mechanical typegauge and the water column test gau
10b) Start the dryer ... with the burner on, the correct water column (W.C.) reading ininches should be:When a gas dryer is first started (during ini
11c) Flame Failure ReignitionIf the established flame signal is lost while the burner is operating, the HSI module(controller) will respond within 0
124) HSI (Hot Surface Ignition) 24 VAC TransformerThe HSI transformer is designed to step down the operating voltage of the dryer to24 VAC to operate
13(2) With a meter (either a multimeter or ohmmeter) set on the 200 ohm position,place the meter leads across:(a) Terminals 1 and 2...the reading shou
14E. PARTS LIST (basic)When ordering replacement parts from the factory, please specify model number and serialnumber in addition to the part number
15HSI (Hot Surface Ignition) SYSTEM COMPONENTS24 VAC TransformerHot Surface Ignition (HSI) Module36E24 VAC Redundant Gas ValveUpshot Burner TubewithHo
ADC 450401 1-05/20/97-50 2-02/25/98-50
Retain This Manual In A Safe Place For Future ReferenceAmerican Dryer Corporation products embody advanced concepts in engineering, design, and safety
1GAS HOT SURFACE IGNITION (HSI) SYSTEMMODEL TRITON 2465 (ADC Part No. 128974) 50/60 Hz TYPE ONLYPRODUCT INFORMATION and TROUBLESHOOTING GUIDENOTE: F
2A. INTRODUCTIONThe Hot Surface Ignition (HSI) System operates at 24 VAC and is a discrete component basedgas ignition control (HSI module) system whi
324 VAC Transformer(1) Recovery from LOCKOUT requires a manual reset by either resetting thethermostat or removing the 24 VAC from the HSI module for
436E Redundant Gas ValveWARNING: THE HSI GAS VALVES ARE NOT FIELD REPAIRABLE.IMPORTANT:THERE ARE NO PARTS AVAILABLE FOR FIELD REPAIR. Replacegas valv
52. SYSTEM (basic) ELECTRICAL RATINGS/SPECIFICATIONSINPUT POWER CONTROL: 18-30 VAC 50/60 HzINPUT CURRENT DRAIN 300 mA @ 24 VAC with GAS VALVE RELAY
6f. The Hot Surface Ignitor will turn on and after approximately four (4) seconds the HotSurface Ignitor will shut off. The Gas Valve will be energiz
73. NORMAL OPERATION (summary)When a signal is received from the thermostat supplying 24 volts to the W terminal of the HSImodule, the control will r